ATI Systems Provides a TETRA Radio Based Public Address System for HMEL’s Refinery Project in India
The system includes visual strobe alerts, audio tone alerts plus pre-recorded messages and live public address.
ATI Systems provided a state-of-the-art wireless public address system for the state-of-the-art refinery, Guru Gobind Singh Refinery
(GGSR). The independent wireless public address system covers both
indoor and outdoor areas in the refinery complex. It connects to the
fire alarm and telephone systems and it interfaces to the wireless TETRA trunked system. The system includes visual strobe alerts, audio tone alerts plus pre-recorded messages and live public address.
East Boston, MA (PRWEB) August 23, 2012
The independent wireless public
address system covers both indoor and outdoor areas in the refinery
complex. It connects to the fire alarm and telephone systems and it
interfaces to the wireless TETRA trunked system. The system includes
visual strobe alerts, audio tone alerts plus pre-recorded messages and
live public address. The system has two control stations, each of which
monitors and controls the whole system. Outdoor notification is
provided by 38 High Powered Outdoor Speaker Stations, each with 1600
watts of audio power. Indoor notification is handled by 57 Indoor
Speaker Units which control over 900 four-watt speakers distributed
throughout the buildings in the refinery complex. The system also
includes Remote Terminal Units (RTUs)
that control visual warnings and connections to other alert and
communication systems in the refinery. These include: 10 Strobe RTUs
powering 60 strobes, a fire alarm interface RTU, a radio transfer RTU
and one telephone interface unit.
Communication between the control
stations and remote units of the wireless public address system is
accomplished with digital radios using the Terrestrial Trunked Radio
(TETRA) system. TETRA is the European Telecommunications Standards
Institute (ETSI) standard, specifically designed for use by government
agencies, emergency services, for public safety networks, transport
services and the military. The refinery complex uses TETRA
communication and required its use in the public address system. Its
IP-based highly-resilient architecture is implemented at the refinery as
a fully redundant system which offers high flexibility and scalability
as well as a secure environment for routine daily communication
requirements.
Abed Yassine, ATI Systems Vice
President of Operations, was in charge of modifying ATI Systems
equipment to work with the refinery’s communications requirements.
“This system was different from most because of the digital radios,
using the TETRA platform. We usually use radios in analog mode and it
was a challenge to use digital communications, especially sending data
from one-to-many points.” Abed’s engineering team was able to modify
ATI’s equipment to work with the TETRA specifications due to ATI’s
modular, standards-based and flexible system design. “Now we can use
these for other projects as well.”
Security and redundancy were
designed into the wireless public address system at every level. For
system control, there are two ATI Control Stations
located in different buildings. The two control stations are
functionally identical so that if there is a problem at either one of
them the other can take over and control the entire wireless public
address system. Each can communicate with all of the remote units of
the system, as well as each other, to conduct polling, silent tests,
alarm tone activations, pre-recorded messages, and live voice
broadcasts. The status of the wireless plant communication system is
continuously monitored and includes: backup battery and AC power status,
cabinet intrusion, speaker status, radio communications as well as
success or failure of the latest activation or test. Each control
station includes an ATI Communication Control Unit, a computer running ATI’s MassAlert® software and a noise-cancelling microphone for live public address announcements.
ATI’s proprietary MassAlert® software
provides a user friendly interface which is simple, intuitive and easy
to use even in the most stressful emergency situations. It includes
both menu driven functions and a Graphical User Interface (GUI) based on
refinery specific customized maps with icons to show the location and
status of the individual components of the outdoor and indoor warning
system. System activation can be easily controlled from the MassAlert®
software. Activations can consist of tones and pre-recorded messages, or
live audio messages delivered through the noise cancelling microphone.
During and after an activation, the software receives and displays the
success or failure code from each remote unit being activated.
The wireless public address system at HMEL was customized to allow activation of the entire system all at once, or a selective activation of only specific areas of the refinery complex. ATI’s MassAlert® software was configured so that refinery officials can broadcast messages to certain pre-defined zones within the refinery or individual buildings as required by the situation at hand. In addition, the system was designed to allow activation from the master fire alarm control panel. The public address system interfaces with HMEL’s telephone and radio systems such that alert messages are broadcast to the hand-held and base-station TETRA radios, and to the refinery’s EPABX telephones. Using multiple message pathways like this improves the reach of the PA and alert messages throughout the refinery personnel.
The outdoor alert notification is transmitted through 38 High Powered Outdoor Speaker Stations (HPSS16) with 1600 watts of power each. The HPSS16 sirens are placed strategically throughout the refinery complex for proper acoustic coverage. They provide tone alerts as well as intelligible voice notification for pre-recorded messages and live public address. The units are positioned and oriented to minimize echoes, while providing the capability to simultaneously hear announcements and messages from a variety of different directions with minimal sound delay.
In order to alert personnel
within the buildings at the refinery, indoor notification is provided by
911 four-watt speakers located in buildings throughout the refinery.
The speakers are controlled and powered by 57 Indoor Speaker Units (ISUs).
The ISU provides up to 400 watts of continuous audio output power for
reliable alert tone notification, voice instructions and public address,
and is monitored and controlled through the ATI Central Control
Station. Additional notification in the control and classified areas is
provided by 60 strobe lights, powered and controlled by 10 Strobe RTUs.
Visual alerting via strobe can be very useful as in areas where the
ambient noise level is very high.
Source: PRweb